ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/10/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/required documentation and MCP shall be kept in equipment room including wiring diagrams, fire service log, etc. 1/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/required documentation and MCP shall be kept in equipment room including wiring diagrams, fire service log, etc. Not properly documenting visits, inspections, and fire service testing. 2/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 Counterweight hold down clamps need to be set properly. 7/5/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets 2.20.9.4 - Hoist rope tail retaining clips shall be properly spaced & replaced. 7/5/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection incomplete due to shutdown of elevator #1 during test. Still need to test: finals, soft set, UM, light, alarm, phone, EBR. 7/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall be operational with and without main power. 4/21/2023
conversion conversion conversion - reinspect x Left side counter weight derailment wire does not activate seismic feature. 7/2/2018
conversion conversion conversion - reinspect x Remove excess weight from car top. 7/2/2018