MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
: 2-way communication device shall give proper location message, no Location message given.
|
11/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
1/5/21: Car Door restrictor shall work. (REINSPECTION REQUIRED)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
1/5/21: Car Door restrictor shall work. (REINSPECTION REQUIRED)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
1/5/21: Car Door restrictor shall work. (REINSPECTION REQUIRED)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
1/5/21: Reduce door closing force to less than 30# REINSPCTION REQUIRED
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
2016 Compliant MCP shall be kept in equipment room, Fire service testing log shall be recorded monthly
|
5/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.)
|
11/29/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
Hoist ropes shall be replaced (reduced diameter)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
Hoist ropes shall be replaced (reduced diameter)
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide onsite MCP
|
6/3/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide operational telephone in elevator cab
|
12/12/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair/Replace broken Car-top light switch
|
5/3/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE DUE TO INCLEMENT WEATHER. MUST BE COMPLETED WITHIN 30 DAYS.
|
3/30/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE DUE TO INCLEMENT WEATHER. MUST BE COMPLETED WITHIN 30 DAYS.
|
3/30/2022
|