ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.7 - Car door or gate
|
8.11.2.1.1(g)
|
|
|
Door only closes when nudged - safety edge is broken. Reinspection required.
|
8/20/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
2.16
|
|
|
There is no car capacity plate inside the elevator stating the rated load of the car, as required.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.5
|
|
|
The elevator control valve has a permanently mounted pressure gauge. The pressure gauge shall be removed and a quick disconnect fitting shall be installed to allow the control/relief valve to be tested with a properly certified pressure gauge in accordance with A17.1 2004a 3.19.4.5
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
This elevator is required to have a Category 5 weight test performed. The last confirmed weight test performed on this elevator was in 2014. The weight test shall be performed, and safeties set with a rated load.
|
9/28/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work on 110v emergency power or normal power.
|
|