Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x This elevator is required to have a Category 5 weight test performed. The last confirmed weight test performed on this elevator was in 2014. The weight test shall be performed, and safeties set with a rated load. 9/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16 There is no car capacity plate inside the elevator stating the rated load of the car, as required.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on 110v emergency power or normal power.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 The elevator control valve has a permanently mounted pressure gauge. The pressure gauge shall be removed and a quick disconnect fitting shall be installed to allow the control/relief valve to be tested with a properly certified pressure gauge in accordance with A17.1 2004a 3.19.4.5
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 8.11.2.1.1(g) Door only closes when nudged - safety edge is broken. Reinspection required. 8/20/2020