MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of current state operating certificate must be properly displayed
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7.1.4
|
|
|
Cartop lighting missing both bulbs.
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Pit has plastic oil line running from right cylinder head directly to tank, preventing measurement of oil leakage. Extend line and run into existing 5 gallon bucket in pit.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7.1.4
|
|
|
One bulb still missing from car top, provide.
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Return line is going back to the tank, remove. Place line into can in pit. If hose too short or damaged, replace.
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
x
|
|
OSV is due for testing, provide.
|
|