Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Debris needs to be removed from the pit. Pits shall be kept clean and dry. 7/13/2023
MO Minimum : Elevators (I) - Pits (I)1 Debris needs to be removed from the pit. Pits shall be kept clean and dry.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Auxiliary Power fails to bring the car down and open the doors when normal power is removed. 7/24/2023