Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) All hoisting ropes, when replaced, shall have rope tags. New(er) ropes installed, no tags 1/3/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 2.12.7 Bottom access key switch pushed into door jamb, not useable 2/27/2020