ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED)
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
:Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly.
|
5/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Car Door restrictor shall work. Front and Rear.
|
3/30/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
H(8) Replace missing electrical box cover.
|
5/3/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
H(5) Machine room lighting needs to be repaired
|
5/3/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days
|
3/30/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Car Door restrictor shall work. Front and Rear.
|
3/30/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days
|
3/30/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall give proper location message, no Location message given. (REINSPECTION > 14days)
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Key Switch bezel missing in COP
|
11/29/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Remove/attach styrofoam insulation board at top rear of Hoistway(covering exterior ventilation vent). Currently just wedged behind piping, about to fall.
|
11/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly.
|
11/29/2022
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Car hoist ropes undersized, replace per code
|
8/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide onsite MCP
|
6/3/2024
|