Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required 1/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 8.11.3.1.2 (o) x Hydraulic control valve is leaking during relief valve test. Repair/replace within thirty (30) days. 12/17/2020