ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection)
|
x
|
|
Fire Hat light at recall floor does not illuminate when the elevator is placed in Phase 1 recall.
|
1/23/2024
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
|
8.6.1.7.5 Emergency brake release rescue device does not lift the break to move the car.
|
1/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
1/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The wire on the Second floor spirator is broken. Hoistway doors need to be self Closing.
|
1/23/2024
|