Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 7/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil hose on left cylinder needs to be re-attached for proper measurement of oil loss.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage Oil hose on left cylinder needs to be reattached for proper measurements of oil loss 6/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil hose on left cylinder needs to be re-attached for proper measurement of oil loss
MO Minimum : Elevators (I) - Pits (I)1 pit needs to be cleaned 6/20/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work, needs repair. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit stopped operating during testing. Need to perform testing of fire service and door closing force to complete inspection. Re-inspection required 7/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean oil, water & debris from elevator pit