MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self closing and self locking
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Cover shall be replaced on the machine room light switch
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit shall be cleaned and oil cleaned up
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(k)
|
|
|
Provide feeder location on main line and 110v disconnect.
|
1/26/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
All Fire recall switches in a single building shall be keyed the a like
|
12/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone does not work. Repair
|
10/15/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
|