Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 The car operating panel shall be assigned a unique identification a minimum of 1/2" inches in height and of contrasting color to it's background. Note: This car is marked as car 17 everywhere but is marked car 1 at the car station.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 4/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x All rest required by A17.1 2005 8.11.2 shall be completed. Note: This testing is incomplete. On 10/4/2023 the hoistway was run and the elevator was able to safely lower and hold 125%. All other test have yet to be completed. Neither an annual or a category 5 test were actually completed. In the course of testing a cable came off of a sheave, so the test had to be halted until repairs can be made.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Permanently installed electric lighting shall be provided in all machinery spaces, machine rooms, control spaces, and control rooms. The illumination shall be not less than 200 lx (19 fc) at the floor level. Note: The lighting fixture in front of the machine room closet door isn't working and shall be repaired or replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Fire service shall be tested to complete the annual inspection. 4/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.