ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.12 - Car enclosure
|
2.14
|
|
|
Cab walls must be secured to each other bindings between panels are broken allowing movement between each panel. 2.14.1.2
|
5/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emergency Phone Operable 1.6
|
8/28/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
Must Provide current Annual test tag on Mach. room Fire extinguisher.
|
5/15/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Must provide current Test tag on Mach. room Fire extinguisher. (last tagged 2014). 8.6.1.6.5
|
5/15/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current state operating cert in Mach Room. 5.100(2)
|
5/15/2024
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must Post a current state operating Cert. in Mech. Room. 5.100(2)
|
5/15/2024
|