Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve (Red Tag) x x OSV is leaking hydraulic fluid, repair OSV, test with full load and check tripping speed. Red tagged, Re-inspection required 2/14/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Phase I fire service does not work, needs repair. Re-inspection required 2/14/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 4/22/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Provide existing door open button to work ( hitting floor number opens door). 4/22/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Lobby floors (both) have broken tiles prior to entry to elevator, this is a tripping hazard. Repair as needed. 4/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Battery backup lowering unit is not working properly. 4/29/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Over Speed Valve (Red Tag) x x OSV was tested, passed. However, it is still leaking excessively, RED TAG remains.Repair and retest. 4/29/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Over Speed Valve (Red Tag) x x Overspeed valve is not setting. Overspeed shall function so in case of a pipe burst the car will not free fall into pit. RED TAG 4/29/2024