Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone did not work, needs repaired. Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Access to the machine room needs to be clear and unobstructed. Remove materials from room adjacent to machine room sufficient for clear access
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide up to date MCP documentation.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.26 - Broken rope, chain, or tape switch 8.11.2.1.3(i) Yes Yes Replace slack chain switch. Switch has been wet and is corroded. 8/27/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.5 Yes Yes The door open button shall be operational on fire service 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Phase 1 & Phase 2 fire service key switches shall be keyed the same. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Yes No The keys were not on-site. Could not check COP stop switch or phase 2 fire service. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.3.4.1 Yes No A category 5 full load test is required in 2019. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Phase 1 fire recall shall be operational. (Violation corrected 12/3/2020) Re-Inspection Pending 3/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Pit equipment is rusted. Correct source of water backup. 10/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unable to test safeties due to no documentation. Re-inspection required 1/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Yes No Keys to operate unit shall be available, unable to verify Phase II, no keys. Re-inspection required 1/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Provide existing battery backup lowering unit to work. 6/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work. 6/27/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all the non elevator related items from the elevator machine room. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 11/5/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A written MCP shall be kept in the machine room for each unit 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide up to date MCP documentation. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide current year tested fire extinguisher in the elevator machine room. 11/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Bottom floor hoist way door missing roller, provide. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices No No Provide car door open button to work. (Pushing floor number opens door). 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices No No Car door open button shall operate 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices No No Car door open button shall be operational. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work properly. 11/5/2025
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No OSV is unsealed, provide testing. Record results. 11/5/2025
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No OSV in the pit is unsealed, provide testing. 11/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all the non elevator related items from the elevator machine room. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide up to date MCP documentation. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide current year tested fire extinguisher in the elevator machine room. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work properly. Re-inspection required 4/2/2026
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No OSV is unsealed, provide testing. Record results. 4/2/2026