Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Pit equipment is rusted. Correct source of water backup. 10/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices Car door open button shall be operational.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices Car door open button shall operate
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices Provide car door open button to work. (Pushing floor number opens door).
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A written MCP shall be kept in the machine room for each unit
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Bottom floor hoist way door missing roller, provide.
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV in the pit is unsealed, provide testing.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unable to test safeties due to no documentation. Re-inspection required 1/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Provide existing emergency lights and bell to work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide existing battery backup lowering unit to work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x Keys to operate unit shall be available, unable to verify Phase II, no keys. Re-inspection required 1/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Phase 1 fire recall shall be operational. (Violation corrected 12/3/2020) Re-Inspection Pending 3/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.3.4.1 x A category 5 full load test is required in 2019. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.5 x x The door open button shall be operational on fire service 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Phase 1 & Phase 2 fire service key switches shall be keyed the same. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x The keys were not on-site. Could not check COP stop switch or phase 2 fire service. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.26 - Broken rope, chain, or tape switch 8.11.2.1.3(i) x x Replace slack chain switch. Switch has been wet and is corroded. 8/27/2019