Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.3.4.1 Yes No A category 5 full load test is required in 2019. 11/5/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A written MCP shall be kept in the machine room for each unit 11/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Access to the machine room needs to be clear and unobstructed. Remove materials from room adjacent to machine room sufficient for clear access
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Bottom floor hoist way door missing roller, provide. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices No No Car door open button shall be operational. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices No No Car door open button shall operate 11/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone did not work, needs repaired. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Yes No Keys to operate unit shall be available, unable to verify Phase II, no keys. Re-inspection required 1/26/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No OSV in the pit is unsealed, provide testing. 11/5/2025
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No OSV is unsealed, provide testing. Record results. 11/5/2025
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No OSV is unsealed, provide testing. Record results. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Phase 1 & Phase 2 fire service key switches shall be keyed the same. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Phase 1 fire recall shall be operational. (Violation corrected 12/3/2020) Re-Inspection Pending 3/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Pit equipment is rusted. Correct source of water backup. 10/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices No No Provide car door open button to work. (Pushing floor number opens door). 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide current year tested fire extinguisher in the elevator machine room. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide current year tested fire extinguisher in the elevator machine room. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Provide existing battery backup lowering unit to work. 6/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work properly. 11/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work properly. Re-inspection required 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work. 6/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide up to date MCP documentation.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide up to date MCP documentation. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide up to date MCP documentation. 11/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all the non elevator related items from the elevator machine room. 11/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all the non elevator related items from the elevator machine room. 4/2/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.26 - Broken rope, chain, or tape switch 8.11.2.1.3(i) Yes Yes Replace slack chain switch. Switch has been wet and is corroded. 8/27/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.5 Yes Yes The door open button shall be operational on fire service 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Yes No The keys were not on-site. Could not check COP stop switch or phase 2 fire service. 11/5/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unable to test safeties due to no documentation. Re-inspection required 1/26/2024