ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
8.11.2.1.2(p)
|
x
|
|
1/5/21 Machine bearings or worm/ring need to be repaired/replaced. VERY noisy.
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
8.11.2.1.2(p)
|
x
|
|
1/5/21 Machine bearings or worm/ring need to be repaired/replaced. VERY noisy.
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
1/5/21: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
1/5/21: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED)
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
2.20
|
|
|
1/5/21: 2.20.9.5.4 : Hoist rope retaining clip missing, car side.
|
4/16/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
clean car top
|
1/9/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean Pit.
|
11/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Phase 1 Indicator LED @ 1st Floor not working.
|
11/18/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit lights are burnt out
|
1/9/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide MCP in machine room
|
2/5/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove trash/old parts from machine room. Clean as needed.
|
5/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace non-functional controller cooling fans and keep controller doors closed and latched.
|
5/1/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Replace/repair broken flex connector on governor wiring.
|
5/1/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE.
|
3/30/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE.
|
3/30/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(1) Wire ropes shall be replaced
|
x
|
x
|
UNDERSIZED/DAMAGED ROPES.
|
3/30/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(1) Wire ropes shall be replaced
|
x
|
x
|
UNDERSIZED/DAMAGED ROPES.
|
3/30/2022
|