Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/24/2022
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.10.2.2.1(o) x Install all the required signage in the cab. 10/24/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 8.10.2.2.2(m) x Install electrical covers on all devices missing covers in the machine room. 10/24/2022
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.10.2.2.4(e) x Check hoistway access once installed. 10/24/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Install all hall fixtures. 10/24/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Hoist ropes shall be shortened so that the car has a minimum of 6" of runby and can reach the final limit. This unit has been Red-tagged. Re-inspection required 12/14/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)5 Gate switch exceeds the maximum of 2 inches. Reinspect. 6/18/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Emergency stop not over-ridden during Phase I recall 6/17/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Check all phases of fire service and all initiating devices when the 2nd modernization is completed. (Phase 1 & 2 fire service, smoke detectors, and heat detectors have been checked for this car) 10/24/2022