Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Post correct firefighter instructions inside elevator 11/17/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Replace incorrect firefighter instructions on car operating panel 11/11/2023
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys No No Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operable by the same key 11/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the machine room 11/11/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Test and log firefighter operation monthly 11/17/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside machine room 11/17/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Replace incorrect firefighter operating instructions on car operating panel 12/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No MRL not up to date 12/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 12/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Remove oil from pit floor 1/5/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 1/5/2024
MO Minimum : Elevators (I) - Pits (I)1 No No Clean the oil from the pit floor. 11/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Yes No Keyswitch bezels are illegible. 11/13/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Test emergency power operation 12/13/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency power was not tested. 11/13/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test operation of elevator on emergency power 11/9/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency bell does not operate 10/26/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test operation of elevator on emergency power with an inspector present 11/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No Door pressure exceeds 30# 12/9/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test operation of elevator on emergency power 12/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Door pressure exceeds 30# 10/28/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Momentary operation of door open button allows doors to fully open. 14 days to fix or red tagged 11/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No Door pressure exceeds 30# 11/10/2021