Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door force exceeds 30 # 11/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door force exceeds 30 # 10/24/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door pressure exceeds 30# 10/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Door pressure exceeds 30# 12/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door pressure exceeds 30# 11/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 10/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not operate 10/28/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power was not tested. 11/13/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Firefighter phase 2 operation does not operate. 14 days to fix or elevator is red tagged. 11/17/2020
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operable by the same key. 11/11/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Momentary operation of door open button allows doors to fully open . 14 days to fix or red tagged 11/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records MRL not up to date 12/7/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post correct firefighter instructions inside elevator 11/17/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside machine 11/17/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room 11/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Post emergency evacuation of passengers procedure inside machine room 11/17/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Replace incorrect firefighter instructions on car operating panel 11/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace incorrect firefighter operating instructions on car operating panel 12/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 12/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 1/5/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly 11/17/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operation 12/13/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test operation of elevator on emergency power 11/2/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test operation of elevator on emergency power 12/8/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test operation of elevator on emergency power with an inspector present 11/10/2021