Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Escalators 7.3 - Handrails 1008.2m Handrails Replace both handrails
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 2.26.1.6 Indexing failed right side 9/9/2021
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post current state certificate in machine room 9/9/2021
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post current State certificate in machine room
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post current state certificate in machine room
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post current state certificate in machine room
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records Need a maintenance control program on site posted on controller 9/9/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Bottom demarcation lights not working 7/13/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Repair top and bottom demarcation lights
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails Replace right handrail (cracking)
A17.1-1996 : Escalators 7.5 - Lighting 805.7 Replace bottom demarcation lights
conversion conversion conversion - reinspect x Perform step skirt indexing test 8/31/2018
conversion conversion n/a Replace right handrail 8/13/2018