Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided Yes No Provide a sump pump in the pit. Test the sump pump once installed. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.10.2.2.2(cc)(1) Yes No Provide ascending car overspeed test. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No In car car emergency telephone shall work with 24/7 support. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 8.11.2.1.1(n) Yes No Replace the missing low cab ventilation trim on (2) walls. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Yes No Provide code compliant machine room lighting of 19fc. Currently measured at 3.7fc. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) Yes No Seal all machine room penetrations. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Yes No Remove wire mesh window and enclose hole. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Yes No Steam heater in machine room, if working repair to prevent leaking. If not in use, remove. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Yes No Confirm climate control in elevator machine room. Heat & A/C. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Yes No Remove all foreign wires and cables passing through the elevator machine room. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) Yes No 2.19 - Provide unintended movement test. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) Yes No Seal all penetrations in the hoistway. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) Yes No Provide a counterweight runby sign in the pit. 11/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 8.6.4.11 Yes No 2.10.2 Provide toe board on car top. 11/8/2019