Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Must Enclose intire Hoistway. 10/21/2020
conversion conversion n/a Must replace missing panel on back wall of hoistway at lowest landing. 10/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) x There is no MCP or maintenance contract. 10/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x SOS switch did not kill power to hoist machine. 10/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x 125% test in the down direction always hits the final limit. Take corrective action and re-test. Unit Red Tagged. 10/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There is no MCP or maintenance contract.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No MCP provided due to no maintenance contract.