Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Brake coil shall not be fed off hoist motor circuit. It shall have it's own circuit with two contacts. 1/5/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Unit left out of service. Floor stops need to be adjusted. 1/5/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Unit failed 125% test. Red-tag issued. 3/7/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The remainder of the annual and category 5 test shall be completed. Inspection stopped due to red tag. 3/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in-car alarm does not work. Take corrective action and re-test.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in-car alarm does not work. 3/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency light and alarm shall be operational and shall be equipped with a 4 hour battery back-up. 7/11/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No MCP provided due to no maintenance contract.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There is no MCP due to no maintenance contract.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Rope tags and code data tag required. 1/5/2024
conversion conversion n/a Pit must be enclosed with solid material. 4/30/2020
conversion conversion n/a Must enclose intire hoistway. 4/30/2020
conversion conversion n/a All landings must be enclosed with solid material to a height of 8'. 4/30/2020