MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
conversion
|
conversion
|
n/a
|
|
|
All landings must be enclosed with solid material to a height of 8'.
|
4/30/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Brake coil shall not be fed off hoist motor circuit. It shall have it's own circuit with two contacts.
|
1/5/2024
|
conversion
|
conversion
|
n/a
|
|
|
Must enclose intire hoistway.
|
4/30/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No MCP provided due to no maintenance contract.
|
|
conversion
|
conversion
|
n/a
|
|
|
Pit must be enclosed with solid material.
|
4/30/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Rope tags and code data tag required.
|
1/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency light and alarm shall be operational and shall be equipped with a 4 hour battery back-up.
|
7/11/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in-car alarm does not work.
|
3/7/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in-car alarm does not work. Take corrective action and re-test.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The remainder of the annual and category 5 test shall be completed. Inspection stopped due to red tag.
|
3/7/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
There is no MCP due to no maintenance contract.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Unit failed 125% test. Red-tag issued.
|
3/7/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Unit left out of service. Floor stops need to be adjusted.
|
1/5/2024
|