Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust up-trust/doors for proper clearance to door hanger track, but not exceeding door to sill clearance allowance. (Multiple floors)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 2.18.7 x The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. 10/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 2.18.7 x The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The pit shall be kept clean. 10/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.40 - Maintenance Records 2.26.1.4 Inspection Operation A fire service testing log shall be kept on-site. 10/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.26 - Broken rope, chain, or tape switch 2.26.2.6 x x The broken suspension member (belt) switches (there are 2) shall each stop the car independently. Note: Presently, both switches have to be tripped to stop the car. 8/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work, with and without main power, and give proper location. 10/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work, with and without main power, and give proper location.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 10/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 9/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x The door closing force shall be tested and the results recorded. 9/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Provide category 5 generator test. 9/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.1.2(bb) x Provide testing of car governor and record the electrical tripping and jaw speeds. 9/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Provide a code compliant fire extinguisher near 4th floor elevator lobby entrance. 10/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Phase 1 & Phase 2 fire service operation shall be tested. 9/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 8.11.2.1.4(l) Provide testing of generator selector switch. 10/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, and evacuation procedures. Fire service log to be recorded monthly. Note: Basic MCP is present but none of the required logs for 2021, 2022, and 2023.
conversion conversion conversion - reinspect x Could not test car over speed Governor due to door close button not working. 8/24/2018
conversion conversion n/a Door Close Button does not work and need repair. 6/22/2018