Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up rescue device was tested and did not operate as the instructions stated, the elevator failed to move. Repair the device to operate as it is designed.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Perform the required emergency power testing
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide complete Cat 5 inspection. ( including emergency power) 125% brake test completed(passed).observed pit needed cleaning, observed missing Phase I instructions.Hoistway examination, car top examination,inside car and pit examination completed. 2/11/2025
conversion conversion conversion - reinspect x Emergency phone not working 3/13/2019