A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Observed oil-soaked "oil-dry" material on pit floor.
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
8.11.3.1.1(d)
|
|
|
Landing sill (diamond floor plating) on Floor 2 has come loose.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Oil on pit floor.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In-car two way communication (phone) not operating when 110V power removed.
|
5/10/2022
|