Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In-car two way communication (phone) not operating when 110V power removed. 5/10/2022
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.11.3.1.1(d) Landing sill (diamond floor plating) on Floor 2 has come loose.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Observed oil-soaked "oil-dry" material on pit floor.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Oil on pit floor.