Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP shall be provided. Currently missing rescue plan.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 8.11.2.1.1(g) Adjust the car door clutch for better operation. 6/26/2019
conversion conversion conversion - reinspect x Car emergency telephone shall work. 6/15/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Label disconnects with source location and identification. 6/26/2019
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(p) Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(p) Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Provide "In case of fire" signage at all hall station push buttons. 1/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 8.11.2.1.3(z) Provide governor rope data tags. 6/26/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Provide hoist rope data tags. 6/26/2019
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.1 x Rope gripper shall stop the car within 48". The rope gripper operation shall be code compliant - Elevator Red Tagged 10/22/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 3/18/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 5/26/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 10/22/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 2/12/2021
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.6.1.7 The governor encoder cable is not connected. If device is not needed, properly remove wiring and device.
A17.1-2016 : Elevators 2.28 - Terminal stopping devices 8.11.2.1.2(dd) x The governor encoder cable is not connected. If device is not needed, properly remove wiring and device. 10/22/2020
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(f) The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(f) The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Unit shall have on-site maintenance documents.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Unit shall have on-site maintenance documents.