ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP shall be provided. Currently missing rescue plan.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.7 - Car door or gate
|
8.11.2.1.1(g)
|
|
|
Adjust the car door clutch for better operation.
|
6/26/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car emergency telephone shall work.
|
6/15/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate in the elevator machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate in the elevator machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
Label disconnects with source location and identification.
|
6/26/2019
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
|
|
Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect.
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
|
|
Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.1.4(l)
|
x
|
x
|
Provide "In case of fire" signage at all hall station push buttons.
|
1/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.11.2.1.3(z)
|
|
|
Provide governor rope data tags.
|
6/26/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
Provide hoist rope data tags.
|
6/26/2019
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
2.19.1
|
|
x
|
Rope gripper shall stop the car within 48". The rope gripper operation shall be code compliant - Elevator Red Tagged
|
10/22/2020
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.2.1.5(a)
|
|
|
The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.2.1.5(a)
|
|
|
The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating.
|
3/18/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating.
|
5/26/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating.
|
10/22/2020
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating.
|
2/12/2021
|
A17.1-2016 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
8.6.1.7
|
|
|
The governor encoder cable is not connected. If device is not needed, properly remove wiring and device.
|
|
A17.1-2016 : Elevators
|
2.28 - Terminal stopping devices
|
8.11.2.1.2(dd)
|
x
|
|
The governor encoder cable is not connected. If device is not needed, properly remove wiring and device.
|
10/22/2020
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(f)
|
|
|
The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting.
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(f)
|
|
|
The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Unit shall have on-site maintenance documents.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Unit shall have on-site maintenance documents.
|
|