Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP shall be provided. Currently missing rescue plan.
conversion conversion conversion - reinspect x Car emergency telephone shall work. 6/15/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Label disconnects with source location and identification. 6/26/2019
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(p) Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Provide "In case of fire" signage at all hall station push buttons. 1/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 8.11.2.1.3(z) Provide governor rope data tags. 6/26/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Provide hoist rope data tags. 6/26/2019
conversion conversion n/a Remove water from the pit. 3/6/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The car door restrictor shall be operational. 2/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The car door restrictor shall be operational. 3/18/2021
A17.1-2016 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) The car top emergency exit shall be properly secured.
A17.1-2016 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) The car top emergency exit shall be properly secured.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The emergency lighting shall be operational. 2/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 3/18/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 2/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. 5/26/2021
A17.1-2016 : Elevators 2.28 - Terminal stopping devices 8.11.2.1.2(dd) x The governor encoder cable is not connected. If device is not needed, properly remove wiring and device. 2/12/2021
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(f) The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Unit shall have on-site maintenance documents.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) x x Upon detection of unintended motion, the rope gripper shall activate and prevent the car from moving either direction more than 48". - Elevator Red-Tagged. 7/9/2021