Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work and give proper location (REINSPECTION within 30 days) 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP shall be kept in equipment room, including Testing Procedure(not present) and Fire service testing log, recorded monthly. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine Room Fire Extinguisher shall have current monthly/annual test tag. expired 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 10/29/2020