Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must Make emergency alarm Operable. 8.6.4.15
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Must make Emergency Light operable. 8.4.6.15
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x x Must make Fire Service Phase I Key Switch operable. 2.27.8
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.14 - Supply Piping 8.11.3.1.5(i) slant rod was stricking victalic fitting on oil line at bottom landing 4/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x telephone does not work-line voltage 50 v DC--telephone bad 1/9/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone Failed 2/17/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintance records 4/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency/auxiliary lighting shall work with power loss 4/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records MCP shall be kept in equipment room, including Oil loss log and Fire service testing log, recorded monthly. No MCP, no Oil log. 2016 compliant MCP required as of 1/1/22. 5/23/2022
MO Minimum : Elevators (I) - Pits (I)1 Sump failed to operate. 6- 8" Water in pit. Repair pump, clean pit equipment. Inspect for water damage. 5/23/2022