A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must Make emergency alarm Operable. 8.6.4.15
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
Must make Emergency Light operable. 8.4.6.15
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
x
|
Must make Fire Service Phase I Key Switch operable. 2.27.8
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.14 - Supply Piping
|
8.11.3.1.5(i)
|
|
|
slant rod was stricking victalic fitting on oil line at bottom landing
|
4/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
telephone does not work-line voltage 50 v DC--telephone bad
|
1/9/2020
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone Failed
|
2/17/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No maintance records
|
4/16/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency/auxiliary lighting shall work with power loss
|
4/14/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
MCP shall be kept in equipment room, including Oil loss log and Fire service testing log, recorded monthly. No MCP, no Oil log. 2016 compliant MCP required as of 1/1/22.
|
5/23/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Sump failed to operate. 6- 8" Water in pit. Repair pump, clean pit equipment. Inspect for water damage.
|
5/23/2022
|