MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
8.6.1.4 :Compliant/Required Documentation & MCP : Fire service testing log must be recorded monthly.
|
1/10/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean. Remove excess debris.
|
1/10/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
8.6.4.9 Cartop shall be cleaned.
|
1/10/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
|
|
17.1-2016:2.7.1.1 Machine/Control Room shall be of fire-resistive construction. **Walls are covered, floor to ceiling, with carpet.** Provide provide approved fire rating documentation or remove.
|
1/10/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device works but extremely faint
|
1/16/2023
|