ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
1) All automatic elevators shall be require a means of two-way communications. Ref: 8.11.2.1.1(f)
|
11/16/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
1) Maintenance records shall document compliance with 8.6 of the Code. There are no maintenance records for this year. Ref: 8.6.1.4.1
|
12/5/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
2) Floors and machinery spaces shall be kept free of water, dirt, rubbish, oil, and grease. There is piles of dust and lint on machine room floor. Ref: 8.6.4.8.1
|
12/5/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
1) Maintenance records shall document compliance with 8.6 of the Code. There are no maintenance records for this year. Ref: 8.6.1.4.1
|
6/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
2) Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Pit needs cleaning. Ref: 8.6.4.7.1
|
6/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an overspeed valve. The valve is sealed but not tagged. Based on the installation year of 2014, a category 5 test is due in 2024.
|
10/17/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/23/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
x
|
|
Unit has an overspeed valve that is due for a 5-year rated load test this year.
|
7/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
3) The following documents specified in 8.6.1.2.2(a), (b), and (c) shall be written and permanently kept on-site in the machine room. All testing procedures shall be on site. Ref: 8.6.1.2.2
|
6/27/2020
|