ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone was not answered
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Do not store non-elevator related items in the machine room
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post a current copy of the state operating certificate in the Elevator machine room. The one that’s on display is several years old.
|
|
conversion
|
conversion
|
n/a
|
|
|
do not store non-elevator relaed equipment in the machine room
|
8/17/2018
|
conversion
|
conversion
|
n/a
|
|
|
repair door restrictor
|
8/17/2018
|
A17.2-2014 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1.18.1(a)
|
|
|
car door restrictor missing parts and needs repaired
|
4/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Repair the door restrictor, it is missing parts
|
10/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, the phone line has dial tone but it would not dial out
|
10/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
need to fill out the monthly fire service test log in the machine room every month
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
post cop of the state operating certificate in the machine room
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post log in the machine room.
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
|
|
remove large peice of PVC pipe laying on the pit floor that is not hooked to anything
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.3 Guards Between Adjacent Pits
|
|
|
2.2.2.6 sumps in pits shall be covered, it is leaning against the wall without the needed cutouts to be installed over the sump hole
|
1/1/2021
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year
|
12/1/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
The firefighters service test log is not being filled out monthly.
|
12/1/2022
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.11.3.1.2(h)
|
|
|
non elevator related material is not to be stored in the elevator machine room
|
12/1/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
water in the oil collection pan
|
12/1/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
the sump pump is plugged in the GFCI outlet, it should be plugged into the single outlet that was provided for the sump pump
|
12/1/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
|
|
water in pit, hydraulic line completely submerged in water, sump pump is not even plugged in, permanent provisions shall be made to prevent accumulation of ground water in the pit
|
7/10/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Water and pit, hydraulic line completely submerged in water, sump pump is not even plugged in, maintain dry pit. Repeat from 2022 (2.2.2.3)
|
6/25/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Do not store non-elevator related items in the machine room (8.6.4.8.2)
|
6/25/2024
|