Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year 12/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No repair door restrictor it is missing parts 11/13/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Perform monthly fire service test and post log in the Machine Room. 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Repair the car door restrictor, it does not work, parts missing 10/12/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes the stop switch in the fire service panel blows a fuse when activated 10/12/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No monthly fire service test log in the machine room is not being filled out monthly 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No post copy of the state operating certificate in the machine room 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps No No elevator cab only has one working ceiling light bulb, required to have minimum working light bulbs, replace burnt out bulbs 7/10/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The state operating certificate in the machine room expired in 2018, update with the new certificate annually 6/25/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.4 - Hoistway door locking devices 2.12 Yes No Top landing hoistway Unlocking device is off and lying on the car top 11/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The state operating certificate in the machine room expired in 2022, update with the new certificate annually 11/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Machine room air conditioning unit is not working, it’s flashing an error. Do not find a remote to operate the air conditioning unit in the machine room. 10/28/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the state operating certificate in the elevator machine room expired in 2018, update with a copy of the current certificate annually 7/10/2023