ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
maintain dry pit, standing water in the pit at the time of the inspection
|
4/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post log in the machine room.
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.1 - Top-of-car stop switch
|
8.11.2.1.3(a)
|
|
|
the car top stop switch on the control station is missing, the stop switch on the pendant station works
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.3 Guards Between Adjacent Pits
|
|
|
clean the pit, oil and water mixture, pistons are starting to rust
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
replace burnt out cab light bulb, only has one working light bulb
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
the monthly fie service test log in the machine room needs to be filled out monthly
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
post copy of the state operating certificate in the machine room
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
replace burnt out cab ceiling light, required to have at least two working light bulbs
|
1/1/2021
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year
|
6/13/2023
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.3.1.1(e)
|
|
|
only one of the cab ceiling lights is working, required to have two working light bulbs
|
6/13/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
sump pump is plugged into the GFCI outlet, it is to be plugged into the non GFCI outlet
|
6/13/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
water, oil, black mold mixture on the pit floor needs to be cleaned up
|
6/13/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the elevator machine room expired in 2018, update with a copy of the current certificate annually
|
6/2/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
replace burnt out light bulb in cab ceiling light fixture, required to have at least two working light bulbs
|
6/2/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
clean the pit, looks like there is mold growing on the pit floor
|
6/2/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
Replace car top light fixture, the fixture is broken in a way that it will not take a light bulb (2.14.7.1.4)
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate in the machine room expired in 2022, update with a new copy of the certificate annually
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean the pit
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.12 - Car enclosure
|
2.14
|
|
|
Replace missing/broken trim ring on the car operating panel (2.14.1.2.4)
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate in the machine room expired in 2022, update with a new copy of the certificate annually
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
|
|
Heat detector in the pit is not to hang by the wires, mount detector to the wall box
|
|
conversion
|
conversion
|
n/a
|
|
|
repair door restrictor
|
8/17/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Repair door restrictor, it is missing parts
|
11/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
repair the door restrictor, the hook is on the car top
|
11/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
the door restrictor is missing parts so that it will not work
|
10/12/2020
|