ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
repair the door restrictor, the hook is missing
|
11/9/2021
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.11.3.1.1(r)
|
x
|
|
car door restrictor hook has been removed, repair the door restrictor
|
12/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
only has one working light bulb in the elevator cab ceiling, requited to have at least two working light bulbs
|
6/13/2023
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.3.1.1(e)
|
|
|
only has one working light bulb in the elevator cab ceiling, required to have two working bulbs
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Replace light bulb in car light fixture, only has one working light bulb. minimum requirement is two working light bulbs
|
4/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
only has one working light bulb in the elevator cab ceiling, replace burnt out bulbs
|
7/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
Only has one working light bulb in the elevator cab ceiling, required to have two working light bulbs
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
replace missing light tube in elevator ceiling, required to have two working lights
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post log in the machine room.
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
monthly fire service test log in the machine room is not being filled out monthly
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
machine room fire extinguisher is missing
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide a fire extinguisher in the Machine room
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean the pit, hydraulic oil has overflowed one of the collection pans
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
clean the pit, the pit is full of oily rags
|
7/15/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
sump pump is plugged into the GFCI outlet, the sump pump should be plugged into the single non GFCI outlet that has been provided
|
12/1/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
water in the pit, maintain a dry pit
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
clean the pit, standing oil on the pit floor, oil catch pans full of oil
|
6/13/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.3 Guards Between Adjacent Pits
|
|
|
clean up standing oil in the pit
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
clean pit, maintain dry pit, standing liquids in the pit
|
4/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18
|
|
|
repack the jacks, leaking and overflowing the oil drip pans in the pit
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5 Gland Packings and Seals
|
|
|
Replace packing in the right hand jack as it overflowed the collection pan in between maintenance visits
|
|
conversion
|
conversion
|
n/a
|
|
|
clean elevator pit
|
8/17/2018
|
conversion
|
conversion
|
n/a
|
|
|
repair door restrictor
|
8/17/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
post a current copy of the state operating certificate in the machine room
|
1/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Update the state operating certificate with the new copy annually, the certificate in the machine room is from 2017
|
7/15/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the elevator machine room expired in 2017, update with a copy of the current certificate annually
|
6/13/2023
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The state operating certificate in the machine room is to be updated annually, the certificate in the machine room expired in 2017
|
|