Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The state operating certificate in the machine room is to be updated annually, the certificate in the machine room expired in 2017
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Provide a fire extinguisher in the Machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit, hydraulic oil has overflowed one of the collection pans
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps Only has one working light bulb in the elevator cab ceiling, required to have two working light bulbs
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals Replace packing in the right hand jack as it overflowed the collection pan in between maintenance visits
conversion conversion n/a clean elevator pit 8/17/2018
conversion conversion n/a repair door restrictor 8/17/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting Replace light bulb in car light fixture, only has one working light bulb. minimum requirement is two working light bulbs 4/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits clean pit, maintain dry pit, standing liquids in the pit 4/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service test and post log in the machine room. 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits clean up standing oil in the pit 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 repack the jacks, leaking and overflowing the oil drip pans in the pit 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 monthly fire service test log in the machine room is not being filled out monthly 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate post a current copy of the state operating certificate in the machine room 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps replace missing light tube in elevator ceiling, required to have two working lights 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) machine room fire extinguisher is missing 1/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x repair the door restrictor, the hook is missing 11/9/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year 12/1/2022
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.11.3.1.1(e) only has one working light bulb in the elevator cab ceiling, required to have two working bulbs 12/1/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) sump pump is plugged into the GFCI outlet, the sump pump should be plugged into the single non GFCI outlet that has been provided 12/1/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) water in the pit, maintain a dry pit 12/1/2022
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.11.3.1.1(r) x car door restrictor hook has been removed, repair the door restrictor 12/19/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate in the elevator machine room expired in 2017, update with a copy of the current certificate annually 6/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps only has one working light bulb in the elevator cab ceiling, requited to have at least two working light bulbs 6/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits clean the pit, standing oil on the pit floor, oil catch pans full of oil 6/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Update the state operating certificate with the new copy annually, the certificate in the machine room is from 2017 7/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps only has one working light bulb in the elevator cab ceiling, replace burnt out bulbs 7/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits clean the pit, the pit is full of oily rags 7/15/2024