Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in car not workig 3/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x Mount Fire extinguisher at 1st floor in view of elevator 6/17/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) All documents of maintenance control program to be accessible outside the hoistway 9/28/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Maintenance control program is not being filled out
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(d) Provide complete maintenance control program and post on controller in machine room 9/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Need testing procedures included in MCP
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Perform monthly fire service & document on log in machine room 9/28/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Perform monthly fire service test and document om log in machine room with a maintenance control program
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 Replace missing fire stops on hoistway doors