Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-locking. 3/1/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 Sewer pipe next to the elevator equipment shall be guarded. 3/1/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room roof is leaking onto the elevator equipment. The leaking pipes above the machine room shall be addressed. 3/1/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide on-site maintenance control program. 6/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current year tested fire extinguisher in the elevator machine room.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide existing phone to work (no power). 11/4/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. Note: The closer is broken.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace faded "Do not use elevator in case of fire" signage as needed.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly.