A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
9/13/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Permanent means of air temperature control are inoperable and shall be repaired in order to ensure proper functioning of elevator equipment. Due to this unit being a Machine-room-less elevator, this also includes the vestibule at the top landing.
|
10/4/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
x
|
Governor overspeed switch and jaw failed spin test. Red tagged elevator.
|
10/2/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher on cartop shall be moved to point outside of hoistway accessible to top floor hoistway access door
|
9/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher shall be mounted in the top floor lobby area
|
8/14/2023
|