Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher on cartop shall be moved to point outside of hoistway accessible to top flor hoistway access door 9/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher shall be mounted in the top floor lobby area 8/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.26.2 x x Governor overspeed switch failed. Red tagged unit until repaired. 9/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 Permanent means of air temperature control are inoperable and shall be repaired in order to ensure proper functioning of elevator equipment. Due to this unit being a Machine-room-less elevator, this also includes the vestibule at the top landing. 10/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light is out 10/4/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 9/13/2024