A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
9/13/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Permanent means of air temperature control are inoperable and shall be repaired in order to ensure proper functioning of elevator equipment. Due to this unit being a Machine-room-less elevator, this also includes the vestibule at the top landing.
|
10/4/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher on cartop shall be moved to point outside of hoistway accessible to top floor hoistway access door
|
10/25/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher shall be mounted in the top floor lobby area
|
8/14/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.26.2
|
x
|
x
|
Safeties are stopping the car with its rated load immediately after leaving the floor. Proper stopping distance is not being achieved. Car has been RED TAGGED and remove rom service until repaired and reinspected.
|
1/8/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year test is incomplete. Complete the following when the red tag item is fixed: Setting of the safeties to get a slide measurement, Counter weight buffer, and governor trip speed
|
1/8/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year test is incomplete. Complete the following when the red tag item is fixed: Setting of the safeties to get a slide measurement, Counter weight buffer, and governor trip speed
|