ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail
|
7/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
|
|
Emergency Brake Release is inoperable
|
7/27/2022
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
5/17/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Fire Fighters Operation indicator at the recall floor hall station does not illuminate.
|
5/17/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Emergency Brake release is inoperable. Indicates a drained battery 2.24.8.4
|
5/17/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room.
|
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(t)
|
x
|
|
2.24.8.4 Emergency Brake Release is inoperable. Indicates a drained battery.
|