Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release Emergency Brake Release is inoperable 7/27/2022
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire Fighters Operation indicator at the recall floor hall station does not illuminate. 5/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Emergency Brake release is inoperable. Indicates a drained battery 2.24.8.4 5/17/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room.
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(t) x 2.24.8.4 Emergency Brake Release is inoperable. Indicates a drained battery. 2/15/2024