Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release Emergency Brake Release is inoperable 7/27/2022
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(t) x 2.24.8.4 Emergency Brake Release is inoperable. Indicates a drained battery. 2/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 7/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire Fighters Operation indicator at the recall floor hall station does not illuminate. 5/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Emergency Brake release is inoperable. Indicates a drained battery 2.24.8.4 5/17/2024
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024