ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.5 - Lighting
|
6.2.7.2
|
|
|
Bottom demarcation light not working.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.9 - Treadways
|
6.2.3.5
|
|
|
Broken tread observed on one step(pallet)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
10.1 - Machinery space access, lighting, receptacle, and condition
|
8.11.4.2.1
|
|
|
Clean pit,lower end.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
10.1 - Machinery space access, lighting, receptacle, and condition
|
8.11.4.2.1
|
|
|
Clean truss space & both pits
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.5 - Lighting
|
8.6.11.5(i) Demarcation Lighting Moving Walk (Re-Inspection)
|
x
|
|
Demarcation lights do not work on bottom landing, need repair. Re-inspection required
|
8/12/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.5 - Lighting
|
6.2.7.2
|
|
|
Lower demarcation lights not working
|
|
A17.1-1996 : Escalators
|
7.5 - Lighting
|
1009.2d
|
|
|
Lower level demarcation lights do not work. Reinspect
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
10.1 - Machinery space access, lighting, receptacle, and condition
|
8.11.4.2.1
|
|
|
Need to perform clean down of truss space and pits.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
Provide electrical prints for moving walk
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
Provide MCP where located.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.5 - Lighting
|
8.6.11.5(i) Demarcation Lighting Moving Walk (Re-Inspection)
|
x
|
|
Repair lower landing demarcation lights. Re-inspection required
|
12/5/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.7 - Combplates
|
6.2.3.8
|
|
|
Replace broken comb plate on top landing. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.7 - Combplates
|
6.2.3.8
|
x
|
|
Replace broken comb plates at top & bottom landing. Re-inspection required
|
8/12/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.9 - Treadways
|
8.3.11.1
|
|
|
Replace broken pallet.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.9 - Treadways
|
6.2.3.5
|
x
|
|
Replace pallet with broken tread. Re-inspection required
|
8/12/2024
|
A17.1-1996 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
1206.6a
|
|
|
Upper and lower level machine space needs to be cleaned out.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
10.1 - Machinery space access, lighting, receptacle, and condition
|
8.11.4.2.1
|
|
|
Walk needs a total clean down.
|
|